cveboard RSS feed

CVE-2018-11451

CVE.org · Published

Historical CVEsJSONAI instructions

Record status
Published
Identifier year (not publication year)
2018
Source publication
Source updated
Imported by cveboard
Source snapshot
cve_2026-10-24_midnight_baseline ·

Plain text

CNA source text (English)

A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.33), Firmware variant PROFINET IO for EN100 Ethernet module (All versions), Firmware variant Modbus TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions < V1.22), SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions < V7.80), SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.58). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the affected products. A manual restart is required to recover the EN100 module functionality of the affected devices. Successful exploitation requires an attacker with network access to send multiple packets to the affected products or modules. As a precondition the IEC 61850-MMS communication needs to be activated on the affected products or modules. No user interaction or privileges are required to exploit the vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Scoped product and version facts

Fix information unknown; no fixed version is derived here. Missing information does not prove that no fix exists.

Exploitation unknown; this catalogue does not assess exploitation.

Firmware variant IEC 61850 for EN100 Ethernet module

Vendor
Siemens AG
Product
Firmware variant IEC 61850 for EN100 Ethernet module
Platforms
Unknown
Default status
Unknown
Firmware variant IEC 61850 for EN100 Ethernet module · Scoped product and version facts
Version (version)Status (status)Version scheme (versionType)Exclusive end (lessThan)Inclusive end (lessThanOrEqual)Status changes (at → status)
All versions < V4.33affectedUnavailableUnavailableUnavailableNone listed

Firmware variant PROFINET IO for EN100 Ethernet module

Vendor
Siemens AG
Product
Firmware variant PROFINET IO for EN100 Ethernet module
Platforms
Unknown
Default status
Unknown
Firmware variant PROFINET IO for EN100 Ethernet module · Scoped product and version facts
Version (version)Status (status)Version scheme (versionType)Exclusive end (lessThan)Inclusive end (lessThanOrEqual)Status changes (at → status)
All versionsaffectedUnavailableUnavailableUnavailableNone listed

Firmware variant Modbus TCP for EN100 Ethernet module

Vendor
Siemens AG
Product
Firmware variant Modbus TCP for EN100 Ethernet module
Platforms
Unknown
Default status
Unknown
Firmware variant Modbus TCP for EN100 Ethernet module · Scoped product and version facts
Version (version)Status (status)Version scheme (versionType)Exclusive end (lessThan)Inclusive end (lessThanOrEqual)Status changes (at → status)
All versionsaffectedUnavailableUnavailableUnavailableNone listed

Firmware variant DNP3 TCP for EN100 Ethernet module

Vendor
Siemens AG
Product
Firmware variant DNP3 TCP for EN100 Ethernet module
Platforms
Unknown
Default status
Unknown
Firmware variant DNP3 TCP for EN100 Ethernet module · Scoped product and version facts
Version (version)Status (status)Version scheme (versionType)Exclusive end (lessThan)Inclusive end (lessThanOrEqual)Status changes (at → status)
All versionsaffectedUnavailableUnavailableUnavailableNone listed

Firmware variant IEC104 for EN100 Ethernet module

Vendor
Siemens AG
Product
Firmware variant IEC104 for EN100 Ethernet module
Platforms
Unknown
Default status
Unknown
Firmware variant IEC104 for EN100 Ethernet module · Scoped product and version facts
Version (version)Status (status)Version scheme (versionType)Exclusive end (lessThan)Inclusive end (lessThanOrEqual)Status changes (at → status)
All versions < V1.22affectedUnavailableUnavailableUnavailableNone listed

SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules

Vendor
Siemens AG
Product
SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules
Platforms
Unknown
Default status
Unknown
SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules · Scoped product and version facts
Version (version)Status (status)Version scheme (versionType)Exclusive end (lessThan)Inclusive end (lessThanOrEqual)Status changes (at → status)
All versions < V7.80affectedUnavailableUnavailableUnavailableNone listed

SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules

Vendor
Siemens AG
Product
SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules
Platforms
Unknown
Default status
Unknown
SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules · Scoped product and version facts
Version (version)Status (status)Version scheme (versionType)Exclusive end (lessThan)Inclusive end (lessThanOrEqual)Status changes (at → status)
All versions < V7.58affectedUnavailableUnavailableUnavailableNone listed