  "schemaVersion": 1,
  "attribution": [
    {
      "source": "CISA Known Exploited Vulnerabilities",
      "url": "https://www.cisa.gov/known-exploited-vulnerabilities-catalog",
      "licence": "US government work"
    },
    {
      "source": "GitHub Advisory Database",
      "url": "https://github.com/advisories",
      "licence": "CC BY 4.0"
    },
    {
      "source": "Have I Been Pwned",
      "url": "https://haveibeenpwned.com/",
      "licence": "CC BY 4.0"
    },
    {
      "source": "CVE Program (CVE records)",
      "url": "https://www.cve.org/Legal/TermsOfUse",
      "licence": "CVE Terms of Use",
      "notice": "Copyright © 1999-2026, The MITRE Corporation. CVE is a trademark and the CVE logo is a registered trademark of The MITRE Corporation.",
      "terms": "CVE Usage: MITRE hereby grants you a perpetual, worldwide, non-exclusive, no-charge, royalty-free, irrevocable copyright license to reproduce, prepare derivative works of, publicly display, publicly perform, sublicense, and distribute Common Vulnerabilities and Exposures (CVE™). Any copy you make for such purposes is authorized provided that you reproduce MITRE's copyright designation and this license in any such copy."
    },
    {
      "source": "FIRST EPSS",
      "url": "https://www.first.org/epss/",
      "licence": "free to use; FIRST requests attribution"
    }
  ],
  "record": {
    "id": "CVE-2023-2071",
    "sourceURL": "https://www.cve.org/CVERecord?id=CVE-2023-2071",
    "idYear": 2023,
    "status": "PUBLISHED",
    "publishedAt": "2023-09-12T13:12:42.386Z",
    "updatedAt": "2024-09-25T20:05:52.107Z",
    "importedAt": "2026-10-24T01:56:53.804Z",
    "snapshot": {
      "id": "cve_2026-10-24_midnight_baseline",
      "at": "2026-10-24T00:00:00.000Z",
      "source": "https://github.com/CVEProject/cvelistV5/releases/tag/cve_2026-10-24_0100Z"
    },
    "facts": {
      "title": "FactoryTalk View Machine Edition Vulnerable to Remote Code Execution",
      "summary": "\nRockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.\n\n",
      "affected": [
        {
          "vendor": "Rockwell Automation",
          "product": "Fa",
          "defaultStatus": "unaffected",
          "versions": [
            {
              "version": "<=13.0",
              "status": "affected"
            }
          ]
        }
      ]
    }
  }
}