FINS (Factory Interface Network Service) is a message communication protocol, which is designed to be used in closed FA (Factory Automation) networks, and is used in FA networks composed of OMRON products. Multiple OMRON products that implement FINS protocol contain following security issues -- (1)Plaintext communication, and (2)No authentication required. When FINS messages are intercepted, the contents may be retrieved. When arbitrary FINS messages are injected, any commands may be executed on, or the system information may be retrieved from, the affected device. Affected products and versions are as follows: SYSMAC CS-series CPU Units, all versions, SYSMAC CJ-series CPU Units, all versions, SYSMAC CP-series CPU Units, all versions, SYSMAC NJ-series CPU Units, all versions, SYSMAC NX1P-series CPU Units, all versions, SYSMAC NX102-series CPU Units, all versions, and SYSMAC NX7 Database Connection CPU Units (Ver.1.16 or later)
Scoped product and version facts
Fix information unknown; no fixed version is derived here. Missing information does not prove that no fix exists.
Exploitation unknown; this catalogue does not assess exploitation.
Multiple OMRON products which implement FINS protocol
- Vendor
- OMRON Corporation
- Product
- Multiple OMRON products which implement FINS protocol
- Platforms
- Unknown
- Default status
Unknown
| Version (version) | Status (status) | Version scheme (versionType) | Exclusive end (lessThan) | Inclusive end (lessThanOrEqual) | Status changes (at → status) |
|---|---|---|---|---|---|
| SYSMAC CS-series CPU Units all versions, SYSMAC CJ-series CPU Units all versions, SYSMAC CP-series CPU Units all versions, SYSMAC NJ-series CPU Units all versions, SYSMAC NX1P-series CPU Units all versions, SYSMAC NX102-series CPU Units all versions, and SYSMAC NX7 Database Connection CPU Units Ver.1.16 or later | affected | Unavailable | Unavailable | Unavailable | None listed |