  "schemaVersion": 1,
  "attribution": [
    {
      "source": "CISA Known Exploited Vulnerabilities",
      "url": "https://www.cisa.gov/known-exploited-vulnerabilities-catalog",
      "licence": "US government work"
    },
    {
      "source": "GitHub Advisory Database",
      "url": "https://github.com/advisories",
      "licence": "CC BY 4.0"
    },
    {
      "source": "Have I Been Pwned",
      "url": "https://haveibeenpwned.com/",
      "licence": "CC BY 4.0"
    },
    {
      "source": "CVE Program (CVE records)",
      "url": "https://www.cve.org/Legal/TermsOfUse",
      "licence": "CVE Terms of Use",
      "notice": "Copyright © 1999-2026, The MITRE Corporation. CVE is a trademark and the CVE logo is a registered trademark of The MITRE Corporation.",
      "terms": "CVE Usage: MITRE hereby grants you a perpetual, worldwide, non-exclusive, no-charge, royalty-free, irrevocable copyright license to reproduce, prepare derivative works of, publicly display, publicly perform, sublicense, and distribute Common Vulnerabilities and Exposures (CVE™). Any copy you make for such purposes is authorized provided that you reproduce MITRE's copyright designation and this license in any such copy."
    },
    {
      "source": "FIRST EPSS",
      "url": "https://www.first.org/epss/",
      "licence": "free to use; FIRST requests attribution"
    }
  ],
  "record": {
    "id": "CVE-2025-13824",
    "sourceURL": "https://www.cve.org/CVERecord?id=CVE-2025-13824",
    "idYear": 2025,
    "status": "PUBLISHED",
    "publishedAt": "2025-12-15T15:20:52.952Z",
    "updatedAt": "2025-12-15T17:09:43.346Z",
    "importedAt": "2026-10-24T01:57:24.991Z",
    "snapshot": {
      "id": "cve_2026-10-24_midnight_baseline",
      "at": "2026-10-24T00:00:00.000Z",
      "source": "https://github.com/CVEProject/cvelistV5/releases/tag/cve_2026-10-24_0100Z"
    },
    "facts": {
      "title": "Micro820®, Micro850®,  Micro870® – Specialized Fuzzing Vulnerabilities",
      "summary": "A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.",
      "affected": [
        {
          "vendor": "Rockwell Automation",
          "product": "Micro820®, Micro850®,  Micro870®",
          "defaultStatus": "unaffected",
          "versions": [
            {
              "version": "V23.011  and below",
              "status": "affected"
            },
            {
              "version": "V12.013 and lower",
              "status": "affected"
            },
            {
              "version": "V14.011 and lower",
              "status": "affected"
            }
          ]
        }
      ]
    }
  }
}