cveboard RSS feed

CVE-2026-61884

CVE.org · Published

Historical CVEsJSONAI instructions

Record status
Published
Identifier year (not publication year)
2026
Source publication
Source updated
Imported by cveboard
Source snapshot
cve_2026-10-24_midnight_baseline ·

Plain text

CNA source text (English)

Tycon Systems TPDIN-Monitor-WEB2 Missing Authentication for Critical Function

The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.

Scoped product and version facts

Fix information unknown; no fixed version is derived here. Missing information does not prove that no fix exists.

Exploitation unknown; this catalogue does not assess exploitation.

TPDIN-Monitor-WEB2

Vendor
Tycon Systems
Product
TPDIN-Monitor-WEB2
Platforms
Unknown
Default status
unaffected
TPDIN-Monitor-WEB2 · Scoped product and version facts
Version (version)Status (status)Version scheme (versionType)Exclusive end (lessThan)Inclusive end (lessThanOrEqual)Status changes (at → status)
0affectedcustom2.4.5UnavailableNone listed
2.4.5unaffectedUnavailableUnavailableUnavailableNone listed