CVE-2025-13911
CVE.org · Publicado
- Status do registro
- Publicado
- Ano do identificador (não é o ano de publicação)
- 2025
- Publicação na fonte
- Atualização na fonte
- Importado pelo cveboard
- Snapshot da fonte
- cve_2026-10-24_midnight_baseline ·
Texto da CNA em inglês
Inductive Automation Ignition Execution with Unnecessary Privileges
Ignition by Inductive Automation, when installed with default OS service account settings, may expose the host system to an elevated code execution risk via the gateway backup restore functionality. An authenticated user with Gateway Administrator privileges can import a malicious gateway backup (.gwbk) file containing crafted project resources, scripts, or modules, resulting in code execution on the host system. This affects both Windows and Linux installations. On Windows, default installations often run the Ignition service as NT AUTHORITY\SYSTEM, resulting in code execution with full local system privileges. On Linux, default installations commonly run the Ignition service as root or with elevated privileges. Specific privilege level depends on installation configuration.
Fatos de produtos e versões por escopo
Dados de correção desconhecidos; nenhuma versão corrigida é deduzida aqui. Dados ausentes não comprovam ausência de correção.
Exploração desconhecida; este catálogo não avalia exploração.
Ignition
- Fornecedor
- Inductive Automation
- Produto
- Ignition
- Plataformas
- Desconhecido
- Status padrão
unaffected
| Versão (version) | Status (status) | Esquema de versões (versionType) | Fim exclusivo (lessThan) | Fim inclusivo (lessThanOrEqual) | Mudanças de status (at → status) |
|---|---|---|---|---|---|
| 8.1.x | affected | Indisponível | Indisponível | Indisponível | Nenhuma listada |