cveboard RSS feed

CVE-2022-2502

CVE.org · Published

Historical CVEsJSONAI instructions

Record status
Published
Identifier year (not publication year)
2022
Source publication
Source updated
Imported by cveboard
Source snapshot
cve_2026-10-24_midnight_baseline ·

Plain text

CNA source text (English)

A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.

Scoped product and version facts

Fix information unknown; no fixed version is derived here. Missing information does not prove that no fix exists.

Exploitation unknown; this catalogue does not assess exploitation.

RTU500 series

Vendor
Hitachi Energy
Product
RTU500 series
Platforms
Unknown
Default status
unaffected
RTU500 series · Scoped product and version facts
Version (version)Status (status)Version scheme (versionType)Exclusive end (lessThan)Inclusive end (lessThanOrEqual)Status changes (at → status)
RTU500 series CMU Firmware version 13.3.1affectedUnavailableUnavailableUnavailableNone listed
RTU500 series CMU Firmware version 13.3.2affectedUnavailableUnavailableUnavailableNone listed
RTU500 series CMU Firmware version 13.3.3unaffectedUnavailableUnavailableUnavailableNone listed
RTU500 series CMU Firmware version 13.4.1unaffectedUnavailableUnavailableUnavailableNone listed