A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
Fatos de produtos e versões por escopo
Dados de correção desconhecidos; nenhuma versão corrigida é deduzida aqui. Dados ausentes não comprovam ausência de correção.
Exploração desconhecida; este catálogo não avalia exploração.
RTU500 series
- Fornecedor
- Hitachi Energy
- Produto
- RTU500 series
- Plataformas
- Desconhecido
- Status padrão
unaffected
| Versão (version) | Status (status) | Esquema de versões (versionType) | Fim exclusivo (lessThan) | Fim inclusivo (lessThanOrEqual) | Mudanças de status (at → status) |
|---|---|---|---|---|---|
| RTU500 series CMU Firmware version 13.3.1 | affected | Indisponível | Indisponível | Indisponível | Nenhuma listada |
| RTU500 series CMU Firmware version 13.3.2 | affected | Indisponível | Indisponível | Indisponível | Nenhuma listada |
| RTU500 series CMU Firmware version 13.3.3 | unaffected | Indisponível | Indisponível | Indisponível | Nenhuma listada |
| RTU500 series CMU Firmware version 13.4.1 | unaffected | Indisponível | Indisponível | Indisponível | Nenhuma listada |