cveboard RSS feed

CVE-2023-2071

CVE.org · Published

Historical CVEsJSONAI instructions

Record status
Published
Identifier year (not publication year)
2023
Source publication
Source updated
Imported by cveboard
Source snapshot
cve_2026-10-24_midnight_baseline ·

Plain text

CNA source text (English)

FactoryTalk View Machine Edition Vulnerable to Remote Code Execution

Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.

Scoped product and version facts

Fix information unknown; no fixed version is derived here. Missing information does not prove that no fix exists.

Exploitation unknown; this catalogue does not assess exploitation.

Fa

Vendor
Rockwell Automation
Product
Fa
Platforms
Unknown
Default status
unaffected
Fa · Scoped product and version facts
Version (version)Status (status)Version scheme (versionType)Exclusive end (lessThan)Inclusive end (lessThanOrEqual)Status changes (at → status)
<=13.0affectedUnavailableUnavailableUnavailableNone listed